Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2025 |
COT - RSPL - Plumbing Final |
|
Re-inspection required |
3/11/25: address required on home, sediment trap required at water heater, lock out caps required at A/C condenser refrigerant lines, exterior plastic piping must be coated for UV protection, all hose bibs must be insulated and wrapped. Light in storage not installed |
| 03/13/2025 |
COT - RSPL - Plumbing Final |
|
Passed |
3-13-25, plumbing final approved. |