Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
Permit Number - TC-RES-0424-02260
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2025 | COT - RSME - Mechanical Final | Re-inspection required | 3/11/25: address required on home, sediment trap required at water heater, lock out caps required at A/C condenser refrigerant lines, exterior plastic piping must be coated for UV protection, all hose bibs must be insulated and wrapped. Light in storage not installed | |
| 03/13/2025 | COT - RSME - Mechanical Final | Passed | 3-13-25, all items noted from previous inspection have been corrected. Building final approved for letter of completion. |