Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2026 | COT - RSPL - Plumbing Final | Re-inspection required | All circuits supplying interior living spaces must be AFCI protected. (Living room, dining, bedrooms, etc) Open knockouts at bottom of service panels are not permitted and must be covered House numbers must be on building. Exterior copper lines must be insulated Clean outs must be cut closer to grade. No appliances are installed and therefore cannot be verified at time of inspection for items such as anti tip, washer line hammer arrestor etc. Outlet face plates missing at unit 2 bathroom Hot and cold water lines at water heaters must be insulated T&p line at unit 1 must terminate a 90 degree angle toward grade Provide ladder for rooftop access. |
|
| 08/26/2026 | COT - RSPL - Plumbing Final | Passed |