Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
Permit Number - TC-RES-0424-01956
Inspection Description - RSBU - Building Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2025 | RSBU - Building Final | Re-inspection required | work is not per approved plans | |
| 12/24/2025 | RSBU - Building Final | Re-inspection required | 1-An additional row of footings, posts, and beams have been added at property line that are not shown on approved plans. 2-8x2x5/16” beams are not installed per details 3 and 7 of Sheet S1. 3-8x2 is missing from loner span on East side. 4-Joist are 2x2 per approved plans. 5- Structure as approximately 12’ tall, which is considerably taller than the approved plans show. |