Parcel: 122070740


Addresses:

4411 E WAVERLY ST


Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-RES-0424-01956

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
12/18/2025 RSBU - Building Final  Re-inspection required work is not per approved plans
12/24/2025 RSBU - Building Final  Re-inspection required 1-An additional row of footings, posts, and beams have been added at property line that are not shown on approved plans.
2-8x2x5/16” beams are not installed per details 3 and 7 of Sheet S1.
3-8x2 is missing from loner span on East side.
4-Joist are 2x2 per approved plans.
5- Structure as approximately 12’ tall, which is considerably taller than the approved plans show.