Permit: TC-RES-0423-04541

Parcel: 132111520

Inspection Status: Partial Pass

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
09/10/2024 COT - RSEL - Electrical Final  Partial Pass Inspection was for clearance to TEP. Provide address information on both units. Ground rods in place along with both water and gas bonds for both units. Okay to backfill. 9/10/2024
10/04/2024 COT - RSEL - Electrical Final  Canceled 10/4/24: canceled per contractor
10/30/2024 COT - RSEL - Electrical Final  Re-inspection required 10-30-24-no plans on site. Customer asked to reschedule when ready.
11/01/2024 COT - RSEL - Electrical Final  Not Ready Inspection was for clearance to TEP. Provide address information on both units. Ground rods in place along with both water and gas bonds for both units. Okay to backfill. 9/10/2024
10/4/24: canceled per contractor
10-30-24-no plans on site. Customer asked to reschedule when ready.
11/1/24: not ready
11/05/2024 COT - RSEL - Electrical Final  Re-inspection required 11/5/2024 provide receptacles at counter tops 12" or greater. Two circuits required at kitchen area. Provide arc fault breakers at all living areas. Provide gfci breakers at laundry room areas. Laundry tied in with restroom in first unit. Missing light fixture in closet. Stopped inspection. Other items may occur.
COT - RSEL - Electrical Final  Re-inspection required Inspection was for clearance to TEP. Provide address information on both units. Ground rods in place along with both water and gas bonds for both units. Okay to backfill. 9/10/2024
10/4/24: canceled per contractor
10-30-24-no plans on site. Customer asked to reschedule when ready.
11/1/24: not ready

11/5/2024 provide receptacles at counter tops 12" or greater. Two circuits required at kitchen area. Provide arc fault breakers at all living areas. Provide gfci breakers at laundry room areas. Laundry tied in with restroom in first unit. Missing light fixture in closet. Stopped inspection. Other items may occur.
11/15/24: anti-siphoning devices required at hose bib, exterior plastic piping must be coated for UV protection, hose bib must be insulated and wrapped, screen at dryer vent exhaust must be removed (can only terminate with damper), b-vent at water heater must extend 2' above roof line, supply lines at water heater must be wrapped for UV protection, tape must be removed from double wall pipe at b-vent, pex not allowed for pressure relief discharge, water heater shed must be properly secured, supports required at emt conduit at panel, properly secure dryer exhaust vent, pad at water heater storage must be corrected (2x4 not acceptable), bubble covers required on exterior receptacles, Roof access required, Electrical whip at A/C unit must be properly installed, knockouts at A/C must be sealed, plastic bushing required at A/C unit for thermostat, A/C condensate must properly terminate and must be coated for UV protection. STOPPED INSPECTION NO ACCESS TO UNITS.
11/20/2024 COT - RSEL - Electrical Final  Passed All corrections were made. approved. 11/20/2024