Permit: TC-RES-0423-04209

Parcel: 129053290


Addresses:

2108 E 18TH ST

Inspection Status: Passed

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
03/18/2025 COT - RSME - Mechanical Final  Passed
12/06/2024 COT - RSME - Mechanical Final  Re-inspection required 12/6/24: anti-tip required at range, GFCI required at bathroom within 36" of basin, caulk water closet, properly insulate water lines in closet and seal penetration, exhaust fan missing in bathroom, sub panel not permitted in closet, no power at smoke alarms, revision required for mechanical changes, no roof access. kitchen receptacles must be GFCI.