Inspection Status: Canceled

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
01/26/2024 COT - RSEL - Electrical Final  Canceled NR, cancelled by Contractor
06/30/2023 COT - RSEL - Electrical Final  Re-inspection required 6/29/23 - The following items must be corrected for final.
1. Need 2nd ground rod and both driven to grade and 6' apart minimum.
2. Scrape paint off pipe where bond clamp attaches.
3. Install new correct sized double pole breaker for garage sub panel feeds.
4. Install water bond.
5. Recall for electric final inspection.