Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2024 | COT - RSEL - Electrical Final | Canceled | NR, cancelled by Contractor | |
| 06/30/2023 | COT - RSEL - Electrical Final | Re-inspection required | 6/29/23 - The following items must be corrected for final. 1. Need 2nd ground rod and both driven to grade and 6' apart minimum. 2. Scrape paint off pipe where bond clamp attaches. 3. Install new correct sized double pole breaker for garage sub panel feeds. 4. Install water bond. 5. Recall for electric final inspection. |