Inspection Status: Not Ready
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 08/18/2026 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Not Ready |
Provide two receptacles near refrigerator countertop. Ensure ground screws are in place at all metal boxes. Missing kitchen hood. Receptacle to the right of range has to move over another bay to be within 2’ of range. Add nail plates to lines that are less than an 1 1/4”. Provide straps for flex duct. 4’ from registers and on. Provide grommets for ceiling boxes. Add receptacle in bedroom near closet door opening. Add fire blocking to dropped ceilings. Secure electrical lines at marked areas. Secure flex duct for exhaust fan. Secure pex at main lines. Provide 18” of copper before transitioning to pex. Provide out door receptacle. |
| 09/02/2026 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
Corrections made |