Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-RES-0325-01224
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2026 | COT - RSEL - Electrical Final | Re-inspection required | 3/9/26: multiple receptacles have open ground, grounds and neutrals tied together at sub panel at patio, sub panel will need to be replaced as circuits are being tied in together at breakers, smoke detector required at bedroom, bathroom circuit tied into 40amp laundry circuit, multiple circuits tied in together. Properly label panel | |
| 08/26/2025 | COT - RSEL - Electrical Final | Not Ready |