Permit: TC-RES-0324-01675

Parcel: 130120380


Addresses:

3722 E 32ND ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
04/29/2025 COT - RSBU - Roof NailingĀ  Re-inspection required 4-29-25, anchor bolts are required within 12" of a splice on each side, tighten down anchor bolts at interior walls, add nails to exterior sheathing where over-penetrated nails exist (nails shall be flush with sheathing and shall not over-penetrate more than 1/16th of an inch). Add nails to loose roof panels, approved plans and truss calculations are required to be on site. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED.
07/09/2025 COT - RSBU - Roof NailingĀ  Passed Ok to dry-in roof system.