Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Pass
Inspection History: BULD - Electrical Clearance
Permit Number - TC-RES-0324-01474
Inspection Description - BULD - Electrical Clearance
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2024 | BULD - Electrical Clearance | Partial Pass | Partial pass. Verbal clearance to TEP INCR. 6/4/2024 | |
06/14/2024 | BULD - Electrical Clearance | Passed | Approved - DGC Clearance to TEP is required for the soar meter |