Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2025 | RSBU - Building Final | Not Ready | 01/03/2025 All lumber must be weather treated. Beam B1 at southeast corner needs to be 4X10 and requires LU hangers at joist. Beam B1 running north to south was cut too short on southeast end, it needs to overhang by 1'6'' per plan. |
|
| 01/03/2025 | RSBU - Building Final | Not Ready | 12-27-24, canceled per permit holder. 01/03/2025 All lumber must be weather treated. 1/3/25: plans call for APT4 straps to be installed at beam to post connection (128T straps installed and must be replaced with APT4, 128T connectors are not load rated), B-1 required at south east corner from porch to home with appropriate hangers at 2x8 joist. Hangers missing throughout. Appropriate load rated connectors must be installed. |
|
| 05/20/2025 | RSBU - Building Final | Re-inspection required | 5/20/2025 per previous notes. Provide proper fasteners to ledger attached to west wall. Nails have been bent trying to penetrate block wall. Remove drywall screws from Lu hanger at ridge point. Third post at east end loose from floor attachments. | |
| 12/27/2024 | RSBU - Building Final | Canceled | 12-27-24, canceled per permit holder. |