Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 04/15/2026 Add anchor bolts on exterior bearing walls and shot pins at interior walls as marked, add 2x4 studs 16" o.c. to west wall and 2x6 header with studs, missing jack studs on north large window in bedroom not per plan - upload revision if different. Add two top bracing to A2M trusses per calcs. |
|
| 05/12/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 5.12.26 Post to beam caps are not of equal or greater uplift as called out on plans. Also plans call for each side but at current configuration only one side is capped on each beam at rear patio. Post base at front patio does not meet equal or greater uplift as base called out and on plans. Over penetration at sheathing fasteners throughout, examples marked in red. |
|
| 05/22/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 05/22/2026 All corrections made to prior inspections. |