Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Permit Number - TC-RES-0324-01301

Inspection Description - BULD - Electrical Clearance

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/13/2024 BULD - Electrical Clearance Re-inspection required 9/13/24: Schedule 40 2 1/2" PVC at pedestal and sub panel must be replaced with schedule 80 PVC, Address tag at pedestal must be replaced, copper piping penetrating Lath must be protected from future contact with stucco, gas piping must be bonded, seal all penetrations going through top plate, seal all penetrations through vapor barrier, nail plates required throughout. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
09/20/2024 BULD - Electrical Clearance Passed