Permit: TC-RES-0324-01301

Parcel: 140253120


Addresses:

5958 S STEWART BL

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Underground 

Date Description Inspector Results Comments
09/13/2024 COT - RSEL - Electrical Underground  Re-inspection required 7/25/24: partial for ufer only
9/13/24: Schedule 40 2 1/2" PVC at pedestal and sub panel must be replaced with schedule 80 PVC, Address tag at pedestal must be replaced, copper piping penetrating Lath must be protected from future contact with stucco, gas piping must be bonded, seal all penetrations going through top plate, seal all pegging through vapor barrier, nail plates required throughout. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
09/20/2024 COT - RSEL - Electrical Underground  Passed