Permit: TC-RES-0323-03876

Parcel: 118040180

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
05/03/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 5/3/24: Anchor bolt spacing greater than 32" O.C throughout, anchor bolts missing 12" from edge of sill plate, H2.5 clips need to be properly fastened throughout, sheathing on exterior not fastened per schedule throughout, framing not per plan over existing section of home, Lags bolt missing at garage west wall to ledger 32" O.C. Headers not per plan throughout, vertical fire blocking missing throughout.
06/27/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed