Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 05/03/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
5/3/24: Anchor bolt spacing greater than 32" O.C throughout, anchor bolts missing 12" from edge of sill plate, H2.5 clips need to be properly fastened throughout, sheathing on exterior not fastened per schedule throughout, framing not per plan over existing section of home, Lags bolt missing at garage west wall to ledger 32" O.C. Headers not per plan throughout, vertical fire blocking missing throughout. |
| 06/27/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|