Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 10/05/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
10/5/23: headers at hall entrance, room entrance, bedroom 3 and bedroom 4 not per plan. Plan states (H2) 2-2x8 and all locations listed above have 2-2x6 installed. Anchor bolt missing 12" from end of bottom plate on north side of bedroom 3 (will check at intermediate) |
| 10/10/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|