Inspection Status: Partial Pass
Inspection History: RSBU - Building Final
Permit Number - TC-RES-0323-03511
Inspection Description - RSBU - Building Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2025 | RSBU - Building Final | Partial Pass | 01/17/25 1. Outlets on exterior east side of home does not have any power. 2. Dishwasher is not secured. 3. Missing your admittance valve in kitchen sink. 4. Anti-tamper caps are still missing on A/C condensers. 5. GFCI upstairs in the laundry is tied to balcony GFCI. 6. Master bedroom downstairs is missing supply, air diffuser, and return air diffuser. OK 7. Extra diffuser in living room, might affect air balance. 8. 6 x 6 diffuser missing in powder room downstairs. 9. Stopped inspection too many issues! |
|
02/12/2025 | RSBU - Building Final | Passed | 2-12-25, building final approved. | |
08/18/2023 | RSBU - Building Final | Partial Pass | Partial pass . Pending other inspections. 8/18/2023 |