Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Anchor bolts should be 32"oc, over-penetrated or missing nails at sheathing throughout, loose roofing at marked areas |
| 08/14/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Missing detail 1 at exterior walls. Missing h25 clips at bearing points. Loose anchor bolts throughout. Add anchor bolts to those that are out of the center third of bottom plate. Provide information on bottom plates that do not look like they're treated. Or replace. 8/14/2025 |
| 09/04/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|