Permit: TC-RES-0323-03374

Parcel: 12111199G


Addresses:

4935 E LEE ST

Inspection Status: Passed

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/28/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed Exterior shear wall sheathing is properly nailed on edges and in the field. H2.5 clips are properly nailed to rafters and wall top plate. Okay to foam, lathe, and stucco wall.