Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
06/09/2026 COT - RSBU - Interior Shear Bracing  Not Ready Called multiple times and received no answer nor call back. Got to the site and tried the gate code that was given numerous times and would not open. 6/9/2026
06/10/2026 COT - RSBU - Interior Shear Bracing  Re-inspection required 6/10/26: Fasteners at exterior sheathing shall be 6" o.c at edge and 12" o.c at field (missing throughout), fasteners shall be no closer than 3/8" from edge (throughout), fasteners shall penetrate no more than 1/8" (throughout), anchor bolt spacing required to be 32" o.c per plans, anchor bolt spacing bolts required to be 5/8" (1/2" installed), anchor bolts shall not be closer than 3.5" to edge of sill plate, roof drains not per plan (missing overflow, double studs required at openings greater than 4', 6x6 post required under beam,strapping required at beam to post connection. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
06/23/2026 COT - RSBU - Interior Shear Bracing  Not Ready work incomplete
07/17/2026 COT - RSBU - Interior Shear Bracing  Not Ready
07/28/2026 COT - RSBU - Interior Shear Bracing  Not Ready
07/29/2026 COT - RSBU - Interior Shear Bracing  Passed