Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 02/17/2026 |
COT - RSPL - Plumbing Final |
|
Re-inspection required |
2/17/26: gas piping is currently running through notched eave/ rafter tails (structural members may not be notched or bored to accommodate gas piping unless specifically engineered), engineer fix required for notches made at structural members, gas piping must be properly supported per IFGC 415.1 support of piping, gas piping must be grounded/bonded. |
| 02/24/2026 |
COT - RSPL - Plumbing Final |
|
Partial Pass |
Rough soil in laundry room complete. Domestic water lines to be installed. |
| 03/11/2026 |
COT - RSPL - Plumbing Final |
|
Passed |
3-11-26: corrections made from inspection dated 2/17/26. |