Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-RES-0225-01019

Parcel: 14038250B


Addresses:

6517 S DOWNING AV

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
05/05/2025 COT - RSEL - Electrical Final  Re-inspection required 05/05/25
Missing warning labels. Per NEC 690 and 705, and IRC R324; markings shall consist of the following:
1. Must be UV resistant with engraved or machine, printed letters or electro plating
2. Red background, color white text and line work.
3. Signage cannot be handwritten.
4. Sign she'll be attached to the service equipment with Pop rivets or screws.
06/26/2025 COT - RSEL - Electrical Final  Passed 6.26.26
Label corrections made as requested.