Inspection Status: Not Ready
Inspection History: COT - RSBU - Stem Wall/Retaining Wall
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2025 |
COT - RSBU - Stem Wall/Retaining Wall |
|
Not Ready |
|
| 05/29/2025 |
COT - RSBU - Stem Wall/Retaining Wall |
|
Partial Pass |
See checklist item for detail. |
| 06/16/2025 |
COT - RSBU - Stem Wall/Retaining Wall |
|
Partial Pass |
See checklist for details. Ok to grout after drain holes per plan and grout witness holes are placed, as discussed with contractor. Send pictures of drain holes to Ben Olmstead for Acceptance before grout. Inform Ben Olmstead of when grouting will take place. |
| 06/24/2025 |
COT - RSBU - Stem Wall/Retaining Wall |
|
Partial Pass |
See General comments in checklist 6/24/25. Pictures of grout weepholes were good. Additional pressure weep hole needs to be placed at corners of wall. Call in pre grout inspection for return walls when ready for grout. |
| 07/22/2025 |
COT - RSBU - Stem Wall/Retaining Wall |
|
Partial Pass |
Contractor provided pictures of reinforcing, weep holes for grout and pressure weeps are good on wall returns. Call in for final when cap is finished. |
| 09/23/2025 |
COT - RSBU - Stem Wall/Retaining Wall |
|
Canceled |
Scheduled to verify inspection of covered items. |