Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-RES-0224-01071
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2024 | COT - RSBU - Roof Nailing | Not Ready | 6/7/24: not ready | |
06/26/2024 | COT - RSBU - Roof Nailing | Re-inspection required | 6/7/24: not ready 6/26/24: water hammer arrestor must be accessible, missing water hammer at hot water at laundry box, sediment trap missing at water heater, T&P must terminate to exterior of building, receptacles missing at laundry room, rain cap and storm collar missing at water heater vent, seal all penetrations through top plate, seal all penetrations through vapor barrier, properly secure wiring in wall. Gas piping must be grounded |
|
07/18/2024 | COT - RSBU - Roof Nailing | Passed |