Parcel: 133261500

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-RES-0223-03025

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/06/2025 RSBU - Building Final  Re-inspection required 1. Missing a smoke detector in sleeping area.

2. Dishwasher needs to be anchored down; dishwasher is missing waterhammer arrestor, dishwasher drain needs to be looped and supported.

3. Anti-tip on electric range is missing.

4. Two small appliance circuits are needed in kitchen.

5. Open up dead front on sub panel to verify proper wiring.

6. Remove washing machine to verify water hammer arrestors.

7. No exhaust for kitchen range

8. Mini split is not UL listed.