Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2025 | COT - RSME - Mechanical Final | Re-inspection required | 1/24/25 Not ready, still have pending inspections open. Reschedule when HVAC is installed. |
|
| 05/30/2025 | COT - RSME - Mechanical Final | Re-inspection required | 5-30-25: missing "knockout"at subpanel, label breakers at panel, exterior receptacles must be weather resistant, paint/seal all exterior wood together with condensation line at rooftop, firefoam all penetrations at top plates inside storage structure, install light fixture at storage or cap where no exposed wires are visible, insulate hose bib and wrap with 10 mil tape, install vacuum breaker at hose bib, cut cleanout to grade, seal bathroom water closet, missing receptacle covers on back bedroom together with a smoke detector.Stopped inspection-a reinspection is required and additional items may be added. | |
| 08/18/2025 | COT - RSME - Mechanical Final | Passed | 8.18.25 Satisfactory corrections implemented Passed |