Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-RES-0223-03007

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Not Ready

Date Description Inspector Results Comments
01/17/2024 COT - RSBU - Exterior Clips/Sheathing  Not Ready 1/17/24: not ready
01/18/2024 COT - RSBU - Exterior Clips/Sheathing  Partial Pass 1/17/24: not ready
1/18/24: wall along existing building must have draftstop at 10' intervals. Wall along existing building missing sheathing per plan, ensure all anchor bolts are appropriately spaced ( anchor bolts were being installed during inspection). King stud missing at bedroom 3 opening.
02/21/2024 COT - RSBU - Exterior Clips/Sheathing  Passed