| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2026 | COT - RSEL - Electrical Final | Re-inspection required | 1. Condenser needs to be secured or bolted down. 2. MOP on the condenser is 25 amps, recommend changing breaker from 30 to 20. 3. Outdoor lighting violates Pima country light ordinance, must be fully shielded |
|
| 06/16/2026 | COT - RSEL - Electrical Final | Passed |