Permit: TC-RES-0126-00222

Parcel: 123070050


Addresses:

2422 E DRACHMAN ST

Inspection Status: Re-inspection required

Inspection History: PDSD Building Division SIte Consultation

Date Description Inspector Results Comments
05/28/2026 PDSD Building Division SIte Consultation Re-inspection required 5/28/26: Revision required restroom layout and kitchen layout, all work has been covered and will need to be exposed prior to next inspection to ensure code compliance, bathrooms currently have 14-2 wire for receptacle (required 12-2 with 20Amp breaker), DWV and pex must be pressurized and tested prior to covering walls, properly secure pex lines throughout, properly support DWV throughout, lighting boxes are undersized (6 c.u. In max), two-prong receptacles must be replaced with code compliant receptacles, closet lighting not on approved set of plans, receptacles missing in master bathroom at lav, missing kitchen receptacles at peninsula, hall way lighting not on approved plan set. STOPPED INSPECTION MORE ITEMS MAY BE ADDED
06/10/2026 PDSD Building Division SIte Consultation Not Ready
06/23/2026 PDSD Building Division SIte Consultation Passed