Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2025 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
2/4/25: Sediment trap required at furnace in attic, furnace B-vent requires 6" clearance from combustibles for single wall pipe and 1" clearance for double wall pipe, refrigeration lines on exterior of home must be fully wrapped or coated for UV protection, disconnect box attachment to house must be sealed. |
| 02/11/2025 |
COT - RSME - Mechanical Final |
|
Passed |
2/11/25 corrections made |
| 02/11/2025 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
2/11/25 no answer at door, external pvc still not painted or uv protected |