Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building FinalĀ
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2026 | RSBU - Building FinalĀ | Re-inspection required | 1. Improper counter receptacle spacing ;Missing receptacle on kitchen counter at 48 inches from the last receptacle from the right. 2. Per 2017 NEC section 210.52; Kitchen island receptacles cannot be installed below countertop that extends more than 6 inches; the current condition has the receptacles mounted under a 16 inch overhang. 3. Missing water-hammer arrestors at washing machine, dishwasher and ice maker. 4. Garage entry door needs to be 20 minute fire rated and solid core. 5. Install combination carbon monoxide/smoke detector in hallway. 6. Romex for waste disposal needs to be protected with conduit. |