Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
Permit Number - TC-RES-0125-00323
Inspection Description - COT - RSBU - Preslab
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2026 | COT - RSBU - Preslab | Re-inspection required | 2.12.26 Improper compaction throughout |
|
| 02/13/2026 | COT - RSBU - Preslab | Passed | 02/13/2026 Verified corrections made to same day inspection. Okay for concrete placement. |
|
| 02/13/2026 | COT - RSBU - Preslab | Re-inspection required | 02/13/2026 Three STHD14 holdowns are not on proper side of wall per foundation plan: northwestern corner, northeastern corner, southeastern corner. Add spacer to ABS pipe touching form to allow concrete to flow behind. Compaction is good but a few areas need more tamping. |