Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
Permit Number - TC-RES-0125-00234
Inspection Description - RSBU - Building Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2025 | RSBU - Building Final | Re-inspection required | 24 March 25 1. Openings in risers are greater than 4". Per IRC 2018; R311.7.5.1--At open risers, openings located more than 30 inches (762 mm), as measured vertically, to the floor or grade below shall not permit the passage of a 4-inch-diameter (102 mm) sphere. 2. Handrails are too wide; handrails must have graspable shape typically circular 1-1/4"- 2" diameter. 3. Top 2 risers leading into patio have a height difference of almost 1", you cannot have a risers vary more than 3/8" in height. |
|
| 04/02/2025 | RSBU - Building Final | Passed | 4/2/2025 Approved. All corrections have been made. |