Permit: TC-RES-0124-00542

Parcel: 103213700

Inspection Status: Re-inspection required

Inspection History: COT - RSOL - Electrical Final Solar Project

Date Description Inspector Results Comments
07/11/2024 COT - RSOL - Electrical Final Solar Project Re-inspection required Denied - The revised plans call for #1cu to new sub-panel with 125A main breaker. Installed unidentified aluminum conductors to sub-panel without 125A main to control panel, did not finish inspection. Provide plan on site
08/19/2024 COT - RSOL - Electrical Final Solar Project Passed