Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Gas Pressure Test
Permit Number - TC-RES-0124-00101
Inspection Description - COT - RSPL - Gas Pressure Test
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2025 | COT - RSPL - Gas Pressure Test | Re-inspection required | 2/19/25: Grey water not installed per plans, properly support gas lines in wall at garage, DWV not under test, support pex lines at laundry in wall for laundry box, nail plates required where electrical or plumbing comes within 1 1/4" of face of stud, supply air missing in laundry room, supply air missing in hall way, secure pex at hose bib, nail plate required at kitchen hood duct, fire place vent not installed, gas piping not complete, seal all penetrations at top plate throughout, copper pipe that will be in contact with stucco must be wrapped with 10mil tape for uv protection. STOPPED INSPECTION WILL BE RECALLED WHEN COMPLETED. | |
02/25/2025 | COT - RSPL - Gas Pressure Test | Passed | 2/25/25 Corrections made held pressure |