Inspection Status: Passed
Inspection History: BULD - Electrical Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 05/07/2025 |
BULD - Electrical Clearance |
|
Passed |
5-7-25, panel okay to be energized. Submit RFI to the city for review/approval showing existing 200 amp service to remain. Any work related to panel at this point will be at own risk pending approval. RECN clearance issued to TEP on meter# 164939258. |
| 05/07/2025 |
BULD - Electrical Clearance |
|
Re-inspection required |
5-7-25, missing moisture barrier together with 2 layers of felt paper behind panel. Plans call for a 400 amp service so submit a revision to the city for review and approval showing existing 200 amp service. |