Permit: TC-RES-0123-02358

Parcel: 130111900


Addresses:

2019 S HOLLY SV

Inspection Status: Passed

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
05/07/2025 BULD - Electrical Clearance Passed 5-7-25, panel okay to be energized. Submit RFI to the city for review/approval showing existing 200 amp service to remain. Any work related to panel at this point will be at own risk pending approval. RECN clearance issued to TEP on meter# 164939258.
05/07/2025 BULD - Electrical Clearance Re-inspection required 5-7-25, missing moisture barrier together with 2 layers of felt paper behind panel. Plans call for a 400 amp service so submit a revision to the city for review and approval showing existing 200 amp service.