Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 6/23/25 1. Shearwalls not per plan, over penetration of fasteners, missing fasteners, see areas marked; plans calls for horizontal layout with blocking. 2. Roof sheathing over penetrated and damaged, replace section called out on site. 3. Missing A34s per plan see detail 7. 4. Area 2(east side)on the plan has been framed out with new slab. This was supposed to be existing, Provide revision with footer dimensions. |
|
| 07/03/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 7/3/25 Partial Pass; okay to dry roof. Need revisions for items 1, and 4 from previous inspection. |
|
| 07/21/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Called multiple times and left a voicemail. Got to the job site and no answer at the door. Called before leaving, still no answer. Need access to the site. 7/21/2025 | |
| 07/22/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Not Ready | ||
| 08/22/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |