Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-1225-00768
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 3-6-26: add nails to exterior sheathing at marked locations but have framers re-walk it nd add nails according to plans, add shot pins at 24" o.c.-minimum of 2 per plate and must be installed within 6" from the end of both ends of plate, add anchor bolts to marked locations-a/b's must be installed in middle third of plate and at 32" o.c., add A35's to cross bracing-see plans for information. | |
| 03/10/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 3-10-26: exterior clips/sheathing approved. |