Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-1225-00768

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/06/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 3-6-26: add nails to exterior sheathing at marked locations but have framers re-walk it nd add nails according to plans, add shot pins at 24" o.c.-minimum of 2 per plate and must be installed within 6" from the end of both ends of plate, add anchor bolts to marked locations-a/b's must be installed in middle third of plate and at 32" o.c., add A35's to cross bracing-see plans for information.
03/10/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 3-10-26: exterior clips/sheathing approved.