Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2025 | COT - RSME - Mechanical Final | Re-inspection required | 11/12/25: HCS clean out cap must be properly installed, insulate water line and wrap with UV tape, remove tape from screen vent on north exterior wall, weather strip at main door not installed, great room receptacles on south wall tied into circuit 16 for small appliances, painted receptacles in laundry must be replaced, receptacles must have covers at time of finals, transfer air grille must be installed, a/c condenser requires 3" clearance from grade, heat kit must be marked at air handler, nm cable to air handler must be properly supported and secured. STOPPED INSPECTION MORE ITEMS MAY BE ADDED | |
| 11/18/2025 | COT - RSME - Mechanical Final | Passed | 11.18.2025 Corrections made to 11.12.2025 inspection. |