Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-1224-01405

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/29/2025 COT - RSBU - Roof Nailing  Re-inspection required 4/29/25: Anchor bolt spacing not per plan at shearwalls, 3"x3" washer plates required at SHearwall 11 and greater, fasteners not per schedule throughout, any sill plate 12" or greater require 2 Anchor bolts minimum. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
05/09/2025 COT - RSBU - Roof Nailing  Re-inspection required 5/8/25 see previous notes
05/13/2025 COT - RSBU - Roof Nailing  Re-inspection required (with fee) 5/13/25
1. Whole house is covered in lathe, please remove lathe at all shear walls for fastener inspection.
07/11/2025 COT - RSBU - Roof Nailing  Partial Pass 4/29/25: Anchor bolt spacing not per plan at shearwalls, 3"x3" washer plates required at SHearwall 11 and greater, fasteners not per schedule throughout, any sill plate 12" or greater require 2 Anchor bolts minimum. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.

5/8/25 see previous notes

5/13/25
1. Whole house is covered in lathe, please remove lathe at all shear walls for fastener inspection.

7/11/25: Home has been completely lathed and insulated. Roof has been completely dried in and loaded. Intermediate inspections were never called in. Letters from all contractors will be required to ensure construction meets or exceeds the 2018 irc. Holdowns and anchor bolts were verified by removal of insulation. DWV was tested at open walls.
09/23/2025 COT - RSBU - Roof Nailing  Passed