Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-1224-01404

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Not Ready

Date Description Inspector Results Comments
03/28/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready 28 March 25
Not ready, they are still working.
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 1 April 25
1. Shear wall SW13 calls for AB at 17'' on center.
2. Garage entry door calls for (2)2x6 header
3. 1st Entry window on left side or SE side calls (2)2x6 header
4. Plan calls for a(2) 2x8 header on north garage wall, this is missing and is not called out as an option.
5. Broken 2x4 east kitchen wall.
6. Shot pins missing on no east kitchen sill.
****STOPPED INSPECTION, MORE ITEMS MAYBE ADDED ON NEXT INSPECTION****
04/04/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 4 April 25
1. West shear wall anchors should be 17" on center with 3"x3" washers.
2. Garage entry door calls for (2)2x6 header
3. 1st Entry window on left side or SE side calls (2)2x6 header
04/11/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 11 April 25
Pass