Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSBU - Roof Nailing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2025 | COT - RSBU - Roof Nailing | Not Ready | 28 March 25 Not ready, they are still working. |
|
| 04/01/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 1 April 25 1. Shear wall SW13 calls for AB at 17'' on center. 2. Garage entry door calls for (2)2x6 header 3. 1st Entry window on left side or SE side calls (2)2x6 header 4. Plan calls for a(2) 2x8 header on north garage wall, this is missing and is not called out as an option. 5. Broken 2x4 east kitchen wall. 6. Shot pins missing on no east kitchen sill. ****STOPPED INSPECTION, MORE ITEMS MAYBE ADDED ON NEXT INSPECTION**** |
|
| 04/04/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 4 April 25 1. West shear wall anchors should be 17" on center with 3"x3" washers. 2. Garage entry door calls for (2)2x6 header 3. 1st Entry window on left side or SE side calls (2)2x6 header |
|
| 04/11/2025 | COT - RSBU - Roof Nailing | Passed | 11 April 25 Pass |