Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-1224-01400
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 6/6/25: Anchor bolts required within 12" of edge from sill plate, straps at garage not per plan, fasteners at shearwall at storage first floor must be properly fastened, fasteners not per shearwall at garage, Gabel end bracing at garage missing, fasteners at shearwall shall penetrate no more than 1/8" and shall not be closer than 3/8" from edge, master bath shearwalls not fastened per schedule, stairs missing clips A34 at stringers, rim board not fastened per schedule, | |
| 06/16/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 6/16/25 shear walls in master bath still not nailed per schedule, sister 2 damaged studs in upstairs master bedroom marked | |
| 06/17/2025 | COT - RSBU - Roof Nailing | Passed | 6.17.25 corrections made and approved |