Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
Permit Number - TC-MDP-1224-01399
Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | ABS pipe needs to be supported in garage. (Above ceiling). Add blocking to all registers. Smoke detectors are to close to the walls. See manufacturers specs. Remove electrical wires from gusset plates. Add studs underneath both girder trusses. Ductwork choked in multiple areas. First floor. Remove drywall screws from fan boxes. 3gang box at SGD has been damaged. Verify staples at exterior plumbing walls for penetration. Tape off all tear in duct work. Secondary drain line has to be over a window. Secure ABS pipe mod way. Seal off top penetrations that have been missed. Stopped inspection other items may apply. | |
| 08/04/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 8.4.25 Corrections made as requested in previous inspectors report. No additional items found. |