Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-1224-01396
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2025 | COT - RSBU - Roof Nailing | Re-inspection required | Shear wall 11 and greater require 3"x3" washer plates, shear wall 13 anchor bolts not per schedule, missing anchor bolts throughout, over penetrating nails at shear walls marked, sister damaged king stud at great room window. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. | |
| 05/09/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 5/9/25 see previous notes | |
| 05/13/2025 | COT - RSBU - Roof Nailing | Passed | 5/13/25 Pass |