Parcel: 141461580


Addresses:

9511 E MEOLA DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-1224-01394

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/17/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 17 April 25
1. All shear walls SW11 and greater need a washer at each A.B.
2. A35 missing in middle stringer.
3. Anchor bolt missing in garage east wall.
04/28/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 17 April 25
1. All shear walls SW11 and greater need a washer at each A.B.
2. A35 missing in middle stringer.
3. Anchor bolt missing in garage east wall.

4/28/25: Washers at SW11 anchor bolts must be 3"x3" or larger.
05/05/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required see previous notes
05/06/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed Approved. Corrections were made. 5/6/2025