Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2025 | COT - RSEL - Electrical Final | Partial Pass | 1. Outdoor receptacles needs to be WR rated. 2. Bedroom receptacle on the left wall needs to drop lower or add a new receptacle. 3. Microwave cannot be on small appliance circuit. 4. Dishwasher/garbage disposal receptacle cannot be on small appliance circuit. 5. A/c units are not UL listed. |
|
| 10/06/2025 | COT - RSEL - Electrical Final | Passed | 10.6.2025 Corrections made to 10.01.2025 inspection, secured AC condensers outside, added street address, painted exposed conduit outside. |