Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-1224-01366
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Provide address on site. Provide Approved plans on site prior to inspection. 4/28/2025 | |
| 04/29/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Anchor bolts are loose throughout. Add shot pins at marked areas interior bottom plates. Missing bracing at both A1 and A4 trusses per truss calcs. Loose sheathing at shower in primary bath. Perimeter nailing not per schedule at window in flex room. A7.0 detail 206, 207, and 213 not per plan. 4/29/2025 | |
| 05/01/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Per previous notes. 5/1/20205 | |
| 05/06/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |