Permit: TC-MDP-1223-01926

Parcel: 103193200


Addresses:

2316 W OWL PERCH LP

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 4/23/24: Anchor bolt spacing at shear wall 6 at master bedroom greater then 32" o.c, Anchor bolts required 12" from sill plate edge at shear walls throughout, 3 consecutive M.A.S.A Clips with 1 leg up at south west corner of house, 2x4 missing at back porch beam to post connection (plans call for (2) 2x4 supporting (2)2x6 but (2)2x10 are installed with only (1) 2x4 supporting them), gable end truss bracing not per plan throughout per detail S5.2/5.
04/25/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed