Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
4/23/24: Anchor bolt spacing at shear wall 6 at master bedroom greater then 32" o.c, Anchor bolts required 12" from sill plate edge at shear walls throughout, 3 consecutive M.A.S.A Clips with 1 leg up at south west corner of house, 2x4 missing at back porch beam to post connection (plans call for (2) 2x4 supporting (2)2x6 but (2)2x10 are installed with only (1) 2x4 supporting them), gable end truss bracing not per plan throughout per detail S5.2/5. |
| 04/25/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|